Q1: Chifukwa chiyani kuwirikiza kawiri (150Hz mpaka 200Hz) kuli koyenera pakuyesa -voltage PD pa thiransifoma ya 40 MVA?
A: Tikamayesa kutsekereza kotalika kwa transformer (inter-kutembenuka ndi pakati-gawo), timayika magetsi okwera kwambiri kuposa mtengo wake (nthawi zambiri 1.5x). Tikadagwiritsa ntchito gwero la 50Hz/60Hz, pachimake chitsulo chitha kulowa mu mphamvu ya maginito, zomwe zimapangitsa kuti chisangalalo chiwonjezeke ndikuwononga makhomawo. Malinga ndi maginito flux formula (Φ=U/4.44fNΦ=U/4.44fN), poonjezera ma frequency kufika pa 150Hz kapena 200Hz, titha kupeza mphamvu yoyezetsa kwambiri kwinaku tikusunga core flux pamalo otetezeka, osakwanira{13}.
Q2: Kodi tingakwaniritse bwanji phokoso lakumbuyo la <10pC panthawi yoyesa thiransifoma ya 66kV?
Yankho: Kukwaniritsa phokoso lotsika chotere m'malo akumunda kumafuna njira mwadongosolo:
Sefa pa Hardware: Kugwiritsa Ntchito Variable Frequency Power Source yokhala ndi zosefera zolemera kwambiri-za ntchito ya LC kuti mutseke-phokoso lambiri kuchokera pakusintha kwa IGBT.
Kukhathamiritsa Munda wa Magetsi: Kukhazikitsa chotchinga chachikulu cha Diameter Grading Shield (Corona Ring) pa 66kV bushings kuti muchepetse corona.
Zolinga Zokhazikitsira: Kukhazikitsa-njira imodzi yokhazikitsira nyenyezi kuti mupewe malupu omwe amakhala ngati tinyanga a EMI.
Cabling: Kugwiritsa ntchito zingwe zoyezera-zotchingidwa ziwiri kuti muteteze ma siginecha amtundu wa PD kuti asasokonezedwe ndi malo.
Q3: Ndi njira ziti zopambana / zolephera pakuyesa kwa 66kV transformer PD malinga ndi IEC 60076-3?
A: Kwa ma transformer okhala ndi Um=72.5 kVUm=72.5 kV (kalasi ya 66kV), muyezo umafunika kuti pakatha nthawi yayitali-yowunikira mphamvu yamagetsi (kawirikawiri pa 1.5Um/31.5Um /3), mlingo wa Partial Discharge uyenera kukhala wosachepera 100pC. Chofunika kwambiri, machitidwe a PD ayenera kukhala okhazikika; kukwera kulikonse kosalekeza kwa kuchuluka kwa kutulutsa kapena kugunda kwa mtima munthawi ya mayeso a mphindi 30-60 kumawonedwa ngati kulephera, ngakhale mtengo wake utakhala pansi pa 100pC.
Q4: Kodi ndingagwiritse ntchito AC Hipot Test Transformer m'malo mwa Variable Frequency System?
A:Transformer yoyesera yachikhalidwe imatha kuchita iziOsiyana Source Withstand Test(kutchinjiriza kwakukulu mpaka pansi). Komabe, zili chonchoosayenererakwa otsutsa kwambiriKuyesa kwa Voltagepagawo la 40MVA chifukwa silingapereke ma frequency ofunikira (150Hz+) kuti apewe kuchulukira kwapakati. Kuphatikiza apo, zosinthira zamayesero zachikhalidwe ndizolemetsa kwambiri ndipo zimakhala zovuta kunyamula kupita kuzigawo zakutali za 66kV poyerekeza ndi ma modular Variable Frequency systems.
Q5: Ubwino wogwiritsa ntchito laibulale ya zala za 2D/3D PRPD mu pulogalamu yowunikira ndi yotani?
A: Laibulale ya Phase-Resolved Partial Discharge (PRPD) imalola mainjiniya kupitilira zotsatira zosavuta za "Pass/Fail". Poyerekeza machulukitsidwe (mawonekedwe, malo, ndi ma frequency) ndi nkhokwe ya zolakwika zomwe zimadziwika, makinawo amatha kuzindikira okha mtundu wa zolakwika-monga kutsokomola kwa kondakitala, tinthu tachitsulo toyandama mumafuta, kapena kusoweka kwa zotchingira zolimba. Izi "Katswiri System" amachepetsa kwambiri chiopsezo cha zolakwika za anthu panthawi yowunika deta.