Kodi mfundo yofunikira yamtundu wa resonant AC test system ndi iti?

 May 26, 2026

 Siyani uthenga

 

Q: Kodi dera la SR limagwira ntchito bwanji pakuyezetsa HV, ndipo chifukwa chiyani limakulitsa magetsi?

A: Pakumveka: ωL=1/(ωC). Chiwopsezo chokha chotsalira ndicho kukana kwa dera R. V_out=V_in × Q. Kukweza kwamagetsi kumeneku ndiko maziko a kuyesa kwa SR HV.

Dera: VFD → Exciter TX → Reactor L → Katundu C (chitsanzo)

Masamu:

• Pakuyimba: X_L=X_C → kuchuluka kwa zomwe zimachitika=0. Q=X_L / R=(1/R)√(L/C)

• V_out=V_in × Q. P_mu=P_out / Q.

-chitsanzo chenicheni padziko lonse lapansi - 10 chingwe cha 110 kV XLPE:

• C=2 μF, chandamale V=128 kV. Kayakitala L=50 H. f_res=15.9 Hz.

• Q=50 → exciter imangofunika 128/50=2.56 kV.

• Kutulutsa kofanana: 2,048 kVA. Zolowetsa zenizeni: ~ 6.5 kW (kuchokera pa jenereta yaying'ono).

Zinthu zitatu za resonance:

① Kukonza: ω²=1/(L·C). ② Kukhazikika: ± 0.5 Hz. ③ Chiyero: THD <5% (masefa a tanki ogwirizana).

Ubwino waukulu: Imathetsa mphamvu ya Ferranti (mndandanda wa inductor umalipiritsa capacitance).

Tumizani kufufuza
Tumizani kufufuza