Kodi palibe-kutayika kwa katundu (kutayika kwachitsulo), ndipo kumayesedwa bwanji?

 May 19, 2026

 Siyani uthenga

 

Q: Kodi kwenikweni palibe-kutayika kwa katundu, ndipo njira yoyesera imawoneka bwanji?

 

A: No-load loss (P₀), yomwe imatchedwanso iron loss or core loss, ndi mphamvu yomwe timagwiritsa ntchito thiransifoma ikayatsidwa ndi voliyumu yovoteledwa ndi ma frequency ndi yotsegula yachiwiri-yozungulira.

Zigawo zomwe{0}}zosataya katundu:

• Kutayika kwa maginito (~ 60–70% ya P₀) - mphamvu zosinthira maginito (∝ f × B¹·⁶).

• Kutayika kwa Eddy panopa (~ 25–35% ya P₀) - mafunde ozungulira mu laminations (∝ f² × B² × t²).

• Kutayika kwa dielectric (~ 1-5%) + I²R pamapiritsi oyambirira (osavomerezeka).

 

Njira yoyesera (IEC 60076-1 / IEEE C57.12.90):

Khwerero

Zochita

Zolemba

1

Tsegulani-circuit secondary (LV side)

Onetsetsani kuti chitetezo - chachiwiri chikhoza kufika mphamvu yowopsa

2

Ikani zovotera Uₙ pa zovoteledwa f mpaka choyambirira (mbali ya HV)

Waveform THD <5%

3

Yesani V, I₀, P₀

Gwiritsani ntchito kalasi 0.2 mphamvu analyzer

4

Lembani I₀ ngati % ya oveteredwa panopa

Nthawi zambiri 0.5-5%

5

Zolondola mpaka 20℃reference

Kuwongolera ndikochepa kwa P₀

 

Makhalidwe a P₀:

• Kugawa (100 kVA–2.5 MVA): 0.3–0.8% ya Pₙ

• Mphamvu zapakatikati (5–50 MVA): 0.15–0.4%

• Mphamvu zazikulu (100–500 MVA): 0.08–0.2%

• Amorphous core: ~ 70% kutsika kuposa tirigu-zitsulo zolunjika

 

Kukwera kwa P₀ kumasonyeza: kuwonongeka kwa ma core, akabudula a interlaminar, kusayenda bwino kwa mafupa, ndi kusangalala mopitirira-.

Kuvomereza: kuyeza P₀ Zocheperapo kapena zofanana ndi zotsimikizika + 15% (IEC 60076-1).

Tumizani kufufuza
Tumizani kufufuza