Momwe mungawerengere kuchuluka kwa dongosolo la SR pa chingwe kapena mayeso a GIS?

 May 26, 2026

 Siyani uthenga

 

Q: Ndiyenera kuyesa chingwe cha 220 kV, kutalika kwa 8 km. Ndikufuna chiyero chanji cha SR?

 

A: Masitepe 7: onetsani zofunikira zoyesa → werengerani C → yerekezerani L → phatikiza f_res → onetsetsani mavoti → bwerezani → malizitsani.

Khwerero-ndi{1}} sitepe - 220 kV chingwe, 8 km:

1. IEC 60840: V_kuyesa=2.0 × 127 kV=254 kV. Kutalika kwa 60 min.

2. C ≈ 8 km × 0.2 μF/km=1.6 μF.

3. Ganizirani za 3× 100 kV/2 A ma reactor mofananira: L=26.7 H, f=24.4 Hz.

4. Pakali pano pa 254 kV: I=V × 2πf × C=6.9 A. Koma 3×2A → 6A okwana → OSATI CHABWINO.

5. Sinthani mpaka 3× 100 kV/4 A rectors: zonse I=12 A → OK. P_mu=254×6.9/35=50 kW.

6. Kulemera konse: 3×450 kg + 200 + 150 + 100=~1,800 kg.

 

Chidule cha kukula kwa zochitika zofala:

Zochitika

V_test (kV)

C (μF)

f (Hz)

Analimbikitsa System

33 kV chingwe, 3 km

48

0.6

45

60 kV/2A × 1, 5 kW

110 kV chingwe, 5 km

160

1.0

24

200 kV/4A ×2, 20 kW

220 kV chingwe, 8 km

254

1.6

24

300 kV/4A × 3, 50 kW

400 kV chingwe, 5 km

330

1.0

48

400 kV/2A ×2, 25 kW

GIS 245 kV, 10 bays

230

0.05

80

300 kV/1A ×2, 5 kW

Jenereta 100 MVA

28

2.5

45

30 kV/5A, 10 kW

 

Zikumbutso zofunika kwambiri:

• +20% margin pa rector voltage rating. +30% margin pamlingo wapano.

• Ngati P_in> 100 kW, ganizirani kuyesa kwa magawo (kololedwa ndi milingo yambiri).

• Q yeniyeni ikhoza kukhala yocheperapo poyerekeza ndi - kukonzekera kosamalitsa kumapewa kulephera kwa magawo.

Tumizani kufufuza
Tumizani kufufuza